44
CADDY WOOD ONLY
3.2.3 ELECTRICAL CONNECTIONS
The following instructions do not replace those of the local code.
Installation and verification of this appliance must be done by a qualified
service man.
All wiring from the service panel to the heating unit must comply with the
electrical code in force and all local regulations. It is recommended to feed the
furnace with its own electrical circuit of 15 amps at 120 volts with a breaker (see
wiring diagram).
Installation of the Caddy wood only furnace requires the use of the fan limit
assembly for wood only option (PA00500) which must be purchased separately.
WARNING
ONLY USE WIRES SUITABLE FOR 75°C (167°F).
3.2.3.1 INSTALLATION OF THE FAN LIMIT CONTROL
To install the fan limit control, refer to the assembly manual supplied with the
blower assembly (PA08568), sold separately.
3.2.3.2 SERVOMOTOR INSTALLATION
Install the servomotor on the right side of the front of the furnace; above the door
(use the pre-drilled holes). The chain that links the air inlet damper to the motor
must have a play of 1/8". When there is no call for heat, the air inlet damper must
be completely closed and the chain must be hooked to the servomotor at the “8
o’clock” position*.
*(With all reserve on the minimum air to be increased depending on the type and
quality of the combustible)