Chapter 5 Parameter Guide
Parameter Listing
This chapter describes all of the parameters contained within the IMP+
IMP+IMP+
IMP+.
Application (APP) Menu
P100 Mode of Operation
This parameter sets the mode of operation, when in run mode, and can be set
to one of the following:
Option Description
1= Distance (Default)
Display shows the distance from the
transducer face to the surface.
2= Level Display shows how full the vessel is.
3= Space Display shows how empty a vessel is.
4= Volume
Display shows volume of material in the
vessel
P104 Measurement Units
This parameter sets the units you want to use for programming and display
Option Description
1 = metres All units of measure are METRES
2 = cm All units of measure are CENTIMETRES
3 = mm All units of measure are MILLIMETRES
4 = feet All units of measure are FEET
5 = inches All units of measure are INCHES
P105 Empty Level
This parameter is to be set to the maximum distance from the face of the
transducer to the empty point, in P104 Measurement Units. Note this value
affects span as well, so should be set before span. Default: IMP 3 = 3.00m
(9.84 feet), IMP 6 = 6.00m (19.69 feet) and IMP 10 = 10.00m (32.81 feet).