QUANTECH
152
FORM QTC3-NM1
ISSUE DATE 08/03/2022
SECTION 7 UNIT CONTROLS
TABLE 20 - YORKTALK 2 COMMUNICATIONS DATA MAP (CONTD)
Address Scale
Imperial SI
Point List Description
1
2
3
4
5
6
7
8
9
10
P27
AV21
YT2_ S01_ P27
nvoYTS01p027
SNVT_count_f (51)
ADF 21
0021
x1
None
None
Sys 2 Run Time in seconds
S
S
S
S
S
P28
AV22
YT2_ S01_ P28
nvoYTS01p028
SNVT_count_f (51)
ADF 22
0022
x10
PSI
BAR
Sys 2 Suction Pressure
S
S
S
S
S
P29
AV23
YT2_ S01_ P29
nvoYTS01p029
SNVT_count_f (51)
ADF 23
0023
x10
PSI
BAR
Sys 2 Discharge Pressure
S
S
S
S
S
P30 AV24
YT2_ S01_ P30
nvoYTS01p030 SNVT_count_f (51)
ADF 24 0024 x10
°F °C
Sys 2 Suction Temperature (Cond Unit)
Sys 2 Cooler Inlet Refrigerant Temp (R-407c)
OOOOO
P31
AV25
YT2_ S01_ P31
nvoYTS01p031
SNVT_count_f (51)
ADF 25
0025
x10
°F
°C
Sys 2 Defrost Temperature (HP)
O
O
O
O
O
P32
AV26
YT2_ S01_ P32
nvoYTS01p032
SNVT_count_f (51)
ADF 26
0026
x10
°F (diff)
°C (diff)
Sys 2 Suction Superheat (EEV)
O
O
O
O
O
P33
AV27
YT2_ S01_ P33
nvoYTS01p033
SNVT_count_f (51)
ADF 27
0027
x1
None
None
Sys 2 Anti-Recycle Timer
S
S
S
S
S
P34
AV28
YT2_ S01_ P34
nvoYTS01p034
SNVT_count_f (51)
ADF 28
0028
x10
%
%
Sys 2 EEV Output % (EEV)
O
O
O
O
O
P35
AV29
YT2_ S01_ P35
nvoYTS01p035
SNVT_count_f (51)
ADF 29
0029
x1
None
None
Number of Compressors
S
S
S
S
S
P36
BV5
YT2_ S01_ P36
nvoYTS01p036
SNVT_switch (95)
BD 5
0065
N/A
0/1
0/1
Sys 1 Alarm [0=No Alarm, 1=Alarm]
S
S
S
S
S
P37
BV6
YT2_ S01_ P37
nvoYTS01p037
SNVT_switch (95)
BD 6
0066
N/A
0/1
0/1
Sys 2 Alarm [0=No Alarm, 1=Alarm]
S
S
S
S
S
P38
BV7
YT2_ S01_ P38
nvoYTS01p038
SNVT_switch (95)
BD 7
0067
N/A
0/1
0/1
Evaporator Heater Status
S
S
S
S
S
P39
BV8
YT2_ S01_ P39
nvoYTS01p039
SNVT_switch (95)
BD 8
0068
N/A
0/1
0/1
Evaporator Pump Status
S
S
S
S
S
P40
BV9
YT2_ S01_ P40
nvoYTS01p040
SNVT_switch (95)
BD 9
0069
N/A
0/1
0/1
Sys 1 Comp 1 Run
S
S
S
S
S
P41
BV10
YT2_ S01_ P41
nvoYTS01p041
SNVT_switch (95)
BD 10
0070
N/A
0/1
0/1
Sys 2 Comp 1 Run
S
S
S
S
S
P42 BV11
YT2_ S01_ P42
nvoYTS01p042 SNVT_switch (95)
BD 11 0071 N/A
0/1 0/1
Sys 1 Liquid Line Solenoid Valve
Sys 1 Mode Solenoid Valve (HP)
SSSSS
P43
BV12
YT2_ S01_ P43
nvoYTS01p043
SNVT_switch (95)
BD 12
0072
N/A
0/1
0/1
Sys 1 Hot Gas Bypass Valve
S
S
S
S
S
P44
BV13
YT2_ S01_ P44
nvoYTS01p044
SNVT_switch (95)
BD 13
0073
N/A
0/1
0/1
Sys 1 Comp 2 Run
S
S
S
S
S
P45
BV14
YT2_ S01_ P45
nvoYTS01p045
SNVT_switch (95)
BD 14
0074
N/A
0/1
0/1
Sys 2 Comp 2 Run
S
S
S
S
S
P46 BV15
YT2_ S01_ P46
nvoYTS01p046 SNVT_switch (95)
BD 15 0075 N/A
0/1 0/1
Sys 2 Liquid Line Solenoid Valve
Sys 2 Mode Solenoid Valve (HP)
SSSSS
P47
BV16
YT2_ S01_ P47
nvoYTS01p047
SNVT_switch (95)
BD 16
0076
N/A
0/1
0/1
Lead System [0=Sys1, 1=Sys2]
S
S
S
S
S
P48
BV17
YT2_ S01_ P48
nvoYTS01p048
SNVT_switch (95)
BD 17
0077
N/A
0/1
0/1
Sys 1 Comp 3 Run
S
S
S
S
S
P49
BV18
YT2_ S01_ P49
nvoYTS01p049
SNVT_switch (95)
BD 18
0078
N/A
0/1
0/1
Sys 2 Comp 3 Run
S
S
S
S
S
P50
BV19
YT2_ S01_ P50
nvoYTS01p050
SNVT_switch (95)
BD 19
0079
N/A
0/1
0/1
Chilled Liquid Type [0=Water, 1=Glycol]
S
S
S
S
S
P51
BV20
YT2_ S01_ P51
nvoYTS01p051
SNVT_switch (95)
BD 20
0080
N/A
0/1
0/1
Ambient Control Mode [0=Std Amb, 1=Low Amb]
S
S
S
S
S
P52
BV21
YT2_ S01_ P52
nvoYTS01p052
SNVT_switch (95)
BD 21
0081
N/A
0/1
0/1
Local/Remote Control Mode [0=Local, 1=Remote]
S
S
S
S
S
P53
BV22
YT2_ S01_ P53
nvoYTS01p053
SNVT_switch (95)
BD 22
0082
N/A
0/1
0/1
Units [0=Imperial, 1=SI]
S
S
S
S
S
P54
BV23
YT2_ S01_ P54
nvoYTS01p054
SNVT_switch (95)
BD 23
0083
N/A
0/1
0/1
Lead/Lag Control Mode [0=Manual, 1=Auto]
S
S
S
S
S
P55
BV24
YT2_ S01_ P55
nvoYTS01p055
SNVT_switch (95)
BD 24
0084
N/A
0/1
0/1
Sys 2 Hot Gas Bypass Valve
O
O
O
O
O
P56
MV1
YT2_ S01_ P56
nvoYTS01p056
SNVT_count_f (51)
ADI 1
0030
x1
None
None
Sys 1 Operational Code
S
S
S
S
S
P57
MV2
YT2_ S01_ P57
nvoYTS01p057
SNVT_count_f (51)
ADI 2
0031
x1
None
None
Sys 1 Fault Code
S
S
S
S
S
P58
MV3
YT2_ S01_ P58
nvoYTS01p058
SNVT_count_f (51)
ADI 3
0032
x1
None
None
Sys 2 Operational Code
S
S
S
S
S
P59
MV4
YT2_ S01_ P59
nvoYTS01p059
SNVT_count_f (51)
ADI 4
0033
x1
None
None
Sys 2 Fault Code
S
S
S
S
S
P60
MV5
YT2_ S01_ P60
nvoYTS01p060
SNVT_count_f (51)
ADI 5
0034
x1
None
None
Sys 1 Debug Code
N
N
N
N
N
P61
MV6
YT2_ S01_ P61
nvoYTS01p061
SNVT_count_f (51)
ADI 6
0035
x1
None
None
Sys 1 Condenser Fan Stage
S
S
S
S
S
P62
MV7
YT2_ S01_ P62
nvoYTS01p062
SNVT_count_f (51)
ADI 7
0036
x1
None
None
Sys 2 Debug Code
N
N
N
N
N
P63
MV8
YT2_ S01_ P63
nvoYTS01p063
SNVT_count_f (51)
ADI 8
0037
x1
None
None
Sys 2 Condenser Fan Stage
S
S
S
S
S
P64
MV9
YT2_ S01_ P64
nvoYTS01p064
SNVT_count_f (51)
ADI 9
0038
N
N
N
N
N
P65
MV10
YT2_ S01_ P65 nvoYTS01p065 SNVT_count_f (51)
ADI 10 0039 x1
None None
Unit Control Mode [0=LW, 1=RW, 2=DA, 3=SP,
4=CL, 5=HT]
SSSSS
P66
AV30
YT2_ S01_ P66
nvoYTS01p066
SNVT_count_f (51)
ADF 30
0040
x1
None
None
Anti-Recycle Time Programmed
S
S
S
S
S
P67
AV31
YT2_ S01_ P67
nvoYTS01p067
SNVT_count_f (51)
ADF 31
0041
x10
°F
°C
Leaving Chilled Liquid Temp Cutout
S
S
S
S
S
P68
AV32
YT2_ S01_ P68
nvoYTS01p068
SNVT_count_f (51)
ADF 32
0042
x10
°F
°C
Low Ambient Temp Cutout
S
S
S
S
S
P69 AV33
YT2_ S01_ P69
nvoYTS01p069 SNVT_count_f (51)
ADF 33
0043
x10
PSI BAR Low Suction Pressure Cutout Heating (HP) S S S S S
LON SNVT Type
N2
Metasys
Engineering
Units
Point List Code: S = Standard O = Optional N = Not Available
Eng
Page
Ref
BACnet
Object
Typ/Ins
BACnet Object
Name
LON Profile
Name
Modbus
Scroll BAS(ISN)
Johnson Controls, Inc.
Subject to change without notice.
2 of 6
02/11/2020

Table of Contents

Other manuals for Quantech QTC3150THE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Quantech QTC3150THE and is the answer not in the manual?

Quantech QTC3150THE Specifications

General IconGeneral
BrandQuantech
ModelQTC3150THE
CategoryChiller
LanguageEnglish

Related product manuals