SECTION 2 PRODUCT DESCRIPTION
2
Control Center
All controls are contained in a NEMA 3R/12 cabinet
with hinged outer door and includes a Liquid Crystal
Display with Light Emitting Diode backlighting for
outdoor viewing:
Two display lines
Twenty characters per line
Display/Print Keys
Color coded 12-button non-tactile keypad with sec-
tions for display and print of typical information:
Chilled liquid temperatures
Ambient temperature
System pressures (each circuit)
Operating hours and starts (each compressor)
Print calls up to the liquid crystal display
Operating data for the systems
History of fault shutdown data for up to the last
six fault shutdown conditions.
An RS-232 port, in conjunction with this press-to-
print button, is provided to permit the capability
of hard copy print-outs via a separate printer (by
others)
Entry Keys
This section is used to enter setpoints or modify system
values.
Setpoints Keys
Updating can be performed to:
Chilled liquid temperature setpoint and range
Remote reset temperature range
Set daily schedule/holiday for start/stop
Manual override for servicing
Low and high ambient cutouts
Number of compressors
Low liquid temperature cutout
Low suction pressure cutout
High discharge pressure cutout
Anti-recycle timer (compressor start cycle time)
Anti-coincident timer (delay compressor starts)
Unit Keys
This section is used to:
Set time
Set unit options
Oper Data Key
The microprocessor control center is capable of dis-
playing the following:
Return and leaving liquid temperature
Low leaving liquid temperature cutout setting
Low ambient temperature cutout setting
Outdoor air temperature
English or Metric data
Suction pressure cutout setting
Each system suction pressure
Discharge pressure (optional)
Liquid Temperature Reset via a Johnson Controls
ISN DDC or Building Automation System (by
others) via a 4 mA to 20 mA or 0 VDC to10 VDC
input
Anti-recycle timer status for each system
Anti-coincident system start timer condition
Compressor run status
No cooling load condition
Day, date and time
Daily start/stop times
Holiday status
Automatic or manual system lead/lag control
Lead system denition
Compressor starts and operating hours
(each compressor)
Status of hot gas valves, evaporator heater and fan
operation
Run permissive status
Number of compressors running
Liquid solenoid valve status
Load and unload timer status
Water pump status
Provisions are included for: pumpdown at shutdown;
optional remote chilled water temperature reset and
two steps of demand load limiting from an external
building automation system. Unit alarm contacts are
standard.
The operating program is stored in non-volatile-memo-
ry, battery backed RAM to eliminate chiller failure due
to AC powered failure/battery discharge. Programmed
setpoints are retained in lithium battery-backed RTC
memory for 5 years minimum.

Table of Contents

Other manuals for Quantech QTC3150THE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Quantech QTC3150THE and is the answer not in the manual?

Quantech QTC3150THE Specifications

General IconGeneral
BrandQuantech
ModelQTC3150THE
CategoryChiller
LanguageEnglish

Related product manuals