SECTION 4 INSTALLATION
4
Generally, the thermal dispersion flow switch is
shipped with the unit as a loose part.
To mount the IFM thermal dispersion switch, use the
following guidelines:
Use a pipe coupling to mount the thermal disper-
sion ow switch. The length of the pipe coupling
must be suitable to ensure that the insertion depth
of the sensor is at least 12 mm.
Mount the thermal dispersion ow switch in hori-
zontal pipes from the side. If it has to be mounted
in vertical pipes, mount the switch in the rising
pipes.
Mount the thermal dispersion ow switch on the
top of the horizontal pipes only if the pipe is fully
lled with liquid. Mount the thermal dispersion
ow switch on the bottom of the horizontal pipes
only if the pipe is free from buildup.
Ensure that the sensor tip does not contact the pipe
wall. Do not mount it in a downpipe, in which the
liquid ows downwards.
Avoid turbulence of the liquid resulting from
bends, valves, reducers, and other pipe ttings.
Ensure that the distance from the potential turbu-
lence upstream or downstream of the sensor loca-
tion is at least 5 times of the pipe diameter.
Connect the control monitor with the ow sensor
directly. No extension cable between them is al-
lowed.

Table of Contents

Other manuals for Quantech QTC3150THE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Quantech QTC3150THE and is the answer not in the manual?

Quantech QTC3150THE Specifications

General IconGeneral
BrandQuantech
ModelQTC3150THE
CategoryChiller
LanguageEnglish

Related product manuals