Example
SYST:NETW:STAT "192.168.0.10", "255:255:255:0",
"172.50.0.0"
Characteristics
Firmware version 2.51
SCPI confirmed. No query.
SYSTem:OPTion:CATalog?
Queries the current GUI info line setting. The command returns a string showing the
actual setting.
Example
SYST:OPT:CAT?
Response "MAININFO OFF": no info line is enabled
Response "MAININFO TEXT": GUI display shows text info
Response "MAININFO PATH": GUI display shows path info
Characteristics
Firmware version 2.57
Query only.
SYSTem:OPTion:SET “MAININFO OFF”
Disables the GUI info line. This is the default state.
Example
SYST:OPT:SET ”MAININFO OFF”
Characteristics
Firmware version V2.57
SCPI confirmed. No query.
SYSTem:OPTion:SET “MAININFO PATH”
Enables the path info line. Before enabling it, you must set one valid path by
ROUTe:CLOSe <path_name>. After enabling the path info line for the first time, you
must press the STATUS key on the R&S OSP front panel.
Example
SYST:OPT:SET ”MAININFO PATH”
Characteristics
Firmware version V2.57
SCPI confirmed. No query.