6 | Electrical connection
80.06.415_iVario2-XS-iVarioPro2-S_IM_en_US 37 / 52
3 AC 240 V Power kW Power consump-
tion A
Fuse A Conductor cross-sec-
tion AWG
iVario 2-XS 15 35 45 8
iVario Pro 2-S 22 53 70 6
3 AC 480 V Power kW Power consump-
tion A
Fuse A Conductor cross-sec-
tion AWG
iVario 2-XS 15 18 25 14
iVario Pro 2-S 22 27 35 10
3 AC 440 V /
480 V
Power kW Power consump-
tion A
Fuse A Conductor cross-sec-
tion AWG
iVario 2-XS 13 / 15 17 / 15 25 / 25 14 / 14
iVario Pro 2-S 19 / 22 25 / 27 35 / 35 10 / 10
3 AC 208 V /
240 V
Power kW Power consump-
tion A
Fuse A Conductor cross-sec-
tion AWG
iVario 2-XS 15 / 15 48 / 35 60 / 45 6 / 8
iVario Pro 2-S 23 / 22 64 / 53 70 / 70 6 / 6
6.8 Switch the supply voltage 208 V/240 V
NOTE
Note that the switching of the supply voltage is only possible on devices
with this option.
NOTE
Note that, when the switch position 208V/240V is changed, the options
in the service level also have to be changed.
a The device is switched off.
a All voltage sources are switched off via an external circuit breaker.
a The electrical compartment is open.
1. Check the supply voltage at the connection.
2. Set the voltage at the dip switch in accordance with the supply voltage.