Environment 
Marathon MM  Rev. D7 Jul 2017  25 
5 Environment 
Sensor location depends on the application. Before deciding on a location, you need to be aware of the 
ambient  temperature  of  the  location,  the  atmospheric  quality  of  the  location,  and  the  possible 
electromagnetic interference in that location, according to the sections described above. If you plan to 
use  air  purging,  you  need  to  have  an  air  connection  available.  If  you  are  installing  the  sensor  in  a 
ThermoJacket accessory, you should use the appropriate mounting device. Also, wiring and conduit 
runs must be considered, including computer wiring and connections, if used. 
5.1 Ambient Temperature 
The sensor is designed for measurements in ambient temperatures between 5°C and 65°C (41 to 149°F). 
A water or air cooled housing is available as option to extend the operating range to 120°C (250°F) with 
air cooling and to 175°C (350°F) with water cooling. 
In ambient conditions up to 315°C (600°F), the ThermoJacket housing should be used. When using the 
ThermoJacket, it is strongly recommended to use the supplied air purge to avoid condensation on the 
lens. 
5.2 Atmospheric Quality 
If  the  lens  gets  too  dirty,  it  cannot  detect  enough  infrared  energy  to  measure  accurately.  It is  good 
practice to always keep the lens clean. The air purge helps keep contaminants from building up on the 
lens. If you use the air purge accessory, make sure a filtered air supply with clean dry air at the correct 
air pressure is installed before proceeding with the sensor installation. 
5.3 Electrical Interference 
To minimize measurement errors due to electrical or electromagnetic interference or “noise” be aware 
of the following: 
  Mount  the  electronics  enclosure  as  far  away  as  possible  from  potential  sources  of  electrical 
interference such as motorized equipment producing large step load changes. 
  Use shielded wire for all input and output connections. 
  Make sure the shield wire from the electronics to terminal block cable is earth grounded. 
  For additional protection, use conduit for the external connections. Solid conduit is better than 
flexible conduit in high noise environments. 
  Do not run AC power in the same conduit as the sensor signal wiring.