Installation 
Marathon MM  Rev. D7 Jul 2017  33 
6.4.2 Addressing 
The addressing of a sensor can be done by means of the Control Panel on the back of the sensor or the 
DataTemp  Multidrop  Software  (Menu  <Sensor  Setup>)  that  came  with  your  sensor.  An  alternative 
would be to use the specific interface commands of the sensor in conjunction with a standard terminal 
program (e.g. Windows HyperTerminal), see section 10.12 Command List, page 78. 
If you are installing two or more sensors in a multi-drop configuration, please be aware of the following: 
  Each sensor must have a unique address greater zero. 
  Each sensor must be set to the same baud rate. 
6.4.3 Configuration Procedure 
1.  Attach each unit individually to the computer. 
2.  Start the DataTemp Multidrop Software. 
3.  In the DataTemp Multidrop Startup Wizard, select the correct COM port and ASCII protocol, 
then <Scan All Baud Rates> for a <Single Sensor>. DataTemp Multidrop should find the single 
MM unit connected to the computer serial port. 
4.  Once DataTemp Multidrop is running, go to the <Setup> menu and select <Sensor Setup>. 
5.  In  the  <Sensor  Setup>  menu  select  the  <Advanced  Setup>  tab.  This  tab  contains  the 
Communications Interface menu. The Interface Menu allows you to set the <Polling Address>, 
<Baud Rate> and <RS485 Mode>. Each unit needs a unique address, but the same <Baud Rate> 
and <RS485 Mode> settings. 
6.  Once all the units are addressed, wire up the units in the either the 2-wire or 4-wire multidrop 
manner, keeping all TxA's, TxB's, RxA's and RxB's to be common. 
7.  Now you can run the DataTemp Multidrop Software and by selecting the baud rate that you 
set, the program will quickly identify all of the units attached on the network and you're up and 
running. 
It is also possible to address each unit without the use of the DataTemp Multidrop Software. Once the 
unit is powered up, use the enter and mode buttons on the back panel operator interface and toggle to 
the Multidrop Address field, see section 7.2 Operation Modes, page 34. Use up and down buttons to 
select a unique address for each unit. The units may now be installed in a multidrop network.