Some inputs such as smoke detectors are always armed so they will only be able to display Restore or Alarm. Inputs
such as Entry types are delayed so that at first they will display the disarmed states Normal and Abnormal followed
by Alarm if the timed entry fails.
In order to display a partition‟s status a database has to be created to store the zone names and its partition reference.
Bosch Alarm Panel Interface
It is recommended that the user be familiar with the DS7400Xi panel and has the ability to program PIN codes and
parameters into the panel.
The PC100 interface has been designed to connect the Integra network to the DS7400Xi alarm panel through the
option or keypad bus. It will emulate a keypad when a link has been provided and report status to the Integra
network when included in the list of keypads. If you observe the red and green led associated with the keypad
network you should notice the red LED flashing as it receives data and the green LED flashing as it responds to
polls. The response to polls will only occur under the following conditions:
1) The keypad address is included in the list of keypads programmed in the Integra network
2) The keypad emulation box has been checked.
3) The keypad address has been programmed into the alarm panel.
In order for the alarm panel to poll the emulated keypad the keypad assignment for the alarm panel should be
programmed. Keypad addresses 1-10 connect to the keypad bus and addresses 11-15 is connected to the option bus.
The PC100 can monitor all keypads on the bus that are listed under panel properties “Keypads”.
A Link to an Event will use an emulated keypad to enter a password followed by a command. If the password is not
programmed into the alarm panel no operation will take place. Whenever a command is executed the green
“DIAG2” LED will turn on. The green “DIAG2” LED will turn off when the alarm panel finishes its poll to the
keypad.
Do not overload the power supply by connecting the IRC2000‟s along with their weigand readers to the Bosch +12v
supply.