APPENDIX A: 4” Standard Red Jacket STP Safety Instructions
ATEX Directive 94/9/EC approved Red Jacket Pumps shall be marked with the
following information
Location:
Veeder-Root Company
6
th
Ave. at Burns Crossing
Altoona, PA 16602 USA
Mark ing:
Demko 03 ATEX 0237289X
CE 1180 Ex II2G
Ex ds IIA T3
All submerged turbine pumps, manifolds and associated equipment shall be installed
in accordance with the manufacturer’s installation, operation and service manuals
supplied.
All installations shall provide reliable electrical connection between the
pump/motor, frame, pipe, manifold or junction box and the tank structure for the
electrical protection and equipotential bonding.
The minimum fuel level shall be set 30mm above the highest product intake level at
the bottom of the pump motor.
Where terminal boxes are used for termination of the cables from the motor and the
supply source, they shall be ATEX certified for use in gas group IIA and category 2.
Where a differential pressure switch or transducer is installed, each must be capable
of ensuring that the nominated temperature classification is not exceeded.
Fasteners are non metric. They shall be replaced only by identical fasteners.
Installation Instruction Manual D042-153 is considered a Related Drawing.