EasyManua.ls Logo

Red Jacket Quick-Set P75S1T2 - Installation Testing; To Test Piping

Default Icon
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
Testing The Installation
DANGER! Always disconnect, lock out, and tag the power before starting to service the pump.
When servicing unit use non-sparking tools and use caution when removing or installing equipment to
avoid generating a spark.
To Te st Pip ing
1. Block lines at each dispenser. (Trip dispenser shear valve.) Remove line test plug for this test.
2. Remove protective plug and close pump check valve by turning the vent closing screw clockwise as far down
as possible (see Figure 26).
CAUTION: Excessive pressure (above normal test pressure of 50 - 55 psi [345 - 380 kPa]) may damage
check valve seat and other system components.
Figure 26. Closing the check valve
3. Remove line test port plug and apply line test pressure at line test port (50 psi [345 kPa] maximum) - see
Figure 27.
4. Depressurize the line by reversing Step 2. Replace the protective plug over the vent closing screw.
5. Apply adequate amount of fresh, UL classified for petroleum, non-setting thread sealant on the 1/4” NPT line
test port plug and replace it. Torque the plug to 14 - 24 ft-lbs (19.4 - 29 N•m)
OFF
REMOVE THREADED
PLUG
VENT CLOSING
SCREW
fig21.eps

Related product manuals