Controller
Variomat 1 06.07.2016 Rev. B English
9.2.2
Default settings
The device controller is shipped with the following default settings. Use the Customer menu to adjust these values to local conditions. In
specific cases, it is possible to further adjust the values in the Service menu.
Customer menu
Parameter
Setting
Remarks
Language EN Display language.
Minimum operating pressure "P
0
" 1.8 bar see chapter 7.2 "Determining the P
0
minimum operating
pressure for the controller" on page 36 .
Next maintenance 12 months Time left to the next due maintenance.
Floating alarm contact All see chapter 9.3 "Messages" on page 52 .
Make-up
Maximum make-up quantity 0 Litres Only if make-up has been selected in the customer menu
with “With water meter Yes”.
Maximum make-up time 20 minutes
Maximum make-up cycles 3 cycles within 2 hours
Degassing
Degassing programme Continuous degassing
Continuous degassing time 12 hours Default setting
Softening (Only if "With softening Yes")
Lock make-up No In the case of soft water residual capacity = 0
Hardness reduction 8°dH = TargetActual
Maximum make-up quantity 0 Litres
Soft water capacity 0 Litres
Cartridge replacement 18 months Replace cartridge.