Controller
Variomat 1 06.07.2016 Rev. B English
ER Code
Alarm
Floating
contact
Causes
Remedy
Alarm reset
05 Pump run time - Set value exceeded.
Severe water loss in
the system.
Cap valve at the
intake side closed.
Air in the pump.
Solenoid valve in the
overflow line does not
close.
Check set value in the
Customer or Service menu.
Check the water loss and
correct, if necessary.
Open the cap valve.
Vent the pump.
Check functioning of the
"PV1" solenoid valve.
-
06 Make-up time - Set value exceeded.
Water loss in the
system.
Make-up line not
connected.
Make-up rate
insufficient.
Make-up hysteresis
too low.
Check set value in the
Customer or Service menu.
Check water level.
Connect make-up line
"Quit"
07 Make-up cycles - Set value exceeded. Check set value in the
Customer or Service menu.
Seal any leak in the system.
"Quit"
08 Pressure measurement YES Controller receives
incorrect signal.
Connect the plug.
Check functioning of the
pressure sensor.
Check the cable for damage.
Check the pressure sensor.
"Quit"
09 Level sensor YES Controller receives
incorrect signal.
Check functioning of the load
cell.
Check the cable for damage.
Connect the plug.
"Quit"
10 Maximum pressure - Set value exceeded.
Overflow line
disabled.
Dirt trap clogged.
Check set value in the
Customer or Service menu.
Check functioning of the
overflow line.
Clean the dirt trap.
"Quit"
11 Make-up quantity - "With water meter" must
be activated in the
Customer menu.
Set value exceeded.
Severe water loss in
the system.
Check set value in the
Customer or Service menu.
Check water loss in the system
and repair, if necessary.
"Quit"