05 Pump run time - • Set value exceeded.
• Severe water loss in
the system.
• Cap valve at the
intake side closed.
• Air in the pump.
• Solenoid valve in the
overflow line does not
close.
• Check set value in the
Customer or Service menu.
• Check the water loss and
correct, if necessary.
• Open the cap valve.
• Vent the pump.
• Check functioning of the
"PV1" solenoid valve.
-
06 Make-up time - • Set value exceeded.
• Water loss in the
system.
• Make-up line not
connected.
• Make-up rate
insufficient.
• Make-up hysteresis
too low.
• Check set value in the
Customer or Service menu.
• Check water level.
• Connect make-up line
"Quit"
07 Make-up cycles - Set value exceeded. • Check set value in the
Customer or Service menu.
• Seal any leak in the system.
"Quit"
08 Pressure measurement YES Controller receives
incorrect signal.
• Connect the plug.
• Check functioning of the
pressure sensor.
• Check the cable for damage.
• Check the pressure sensor.
"Quit"
09 Level sensor YES Controller receives
incorrect signal.
• Check functioning of the load
cell.
• Check the cable for damage.
• Connect the plug.
"Quit"
10 Maximum pressure - • Set value exceeded.
• Overflow line
disabled.
• Dirt trap clogged.
• Check set value in the
Customer or Service menu.
• Check functioning of the
overflow line.
• Clean the dirt trap.
"Quit"
11 Make-up quantity - "With water meter" must
be activated in the
Customer menu.
• Set value exceeded.
• Severe water loss in
• Check set value in the
Customer or Service menu.
• Check water loss in the system
and repair, if necessary.
"Quit"