With this parameter, the 1
st
reference sensor for heating
circuit afterheating can be selected.
Sensor 1 store
Arrangement/Heat. circuit/hc/Expert/S1 Store
adjustment range: 1 … 10
factory setting: 4
With this parameter, the 2
nd
reference sensor can be se-
lected for store-dependent afterheating.
Sensor 2 store
Arrangement/Heat. circuit/hc/Expert/S2 store
adjustment range: 1 … 10
factory setting: 5
Select the relay by means of which afterheating is demand-
ed (DSE or heating circuit module).
Allocate minimum runtime and overrun time of the relay.
Afterheating demand
Arrangement/Heat. circuit/hc/Expert/rel. ahoff
selection: „DSE“, „HC1“, „HC2“, „HC3“
factory setting: „DSE“
Arrangement/Heat. circuit/hc/Expert/ah-Min.
adjustment range: 0 … 90 min
factory setting: 0 min
Arrangement/Heat. circuit/hc/Expert/ah
adjustment range: 0 … 1000 s
factory setting: 0 s
The remote control (RTA11-M) allows manual adjustment
of the heating curve (±15 K). The remote control is op-
tional and it is not included in the full kit.
The heating circuit can be switched off manually, if the re-
mote control is set to the position “heating circuit off“.
Heating circuit switched-off means that the heating circuit
pump is switched off and the mixer closed.
Flow temperature is boosted to maximum for rapid heating
when the remote control it is set to “rapid heating“.
Manual correction (remote control)
Arrangement/Heat. circuit/hc/Expert/man. corr.
selection: „Yes“, „No“
factory setting: „No“
Adjustment channel for allocating the remote control sen-
sor. The factory setting is sensor 8.
Sensor remote control
Arrangement/Heat. circuit/hc/Expert/Sen. remote
adjustment range: 1 … 10
factory setting: 8
When this option is activated, the heating circuit opens
(mixer opens) and the heating circuit pump is switched-on
(provided that the chimney sweeper function is active, see
4.4). The protective function of the heating pump maximum
limitation will still be active.
Chimney sweeper
Arrangement/Heat. circuit/hc/Expert/chimney
selection: “Yes“, “No“
factory setting: “No“