EasyManuals Logo

Rhymebus RM6F5 series User Manual

Rhymebus RM6F5 series
195 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #180 background imageLoading...
Page #180 background image
Attachment 2 Default Value List
180
Att.2
Attachment 2 Default Value List
Func.
Name
dEF 60
dEF 50
dEF 52
dEF 53
dEF 57
F_000
Drive Information
F_001
Start Command Selection
3
3
3
3
3
F_002
Frequency
Command Selection
1
2
2
2
2
F_003
Selection of ―STOP‖ Key
Validity
1
1
1
1
1
F_004
Setting Value
(SV)
Selection
1
1
1
1
1
F_005
Auto-Storing of Setting Value
Selection
1
1
1
1
1
F_006
Selection of Main Display
1
7
7
7
7
F_007
Pressure Transducer Setting
10.0
10.0
10.0
10.0
10.0
F_008
Maximum Allowabel
Operating Pressure
100
100
100
100
100
F_009
Starting Frequency
0.5
0.5
0.5
0.5
0.5
F_010
Starting Voltage
8.0
8.0
8.0
8.0
8.0
F_011
Base Frequency
60.0
60.0
60.0
50.0
60.0
F_012
Base Voltage
220.0
220.0
220.0
220.0
220.0
F_013
Selection of Pump Shift
Operation
(Parallel control)
3
3
3
3
3
F_015
Control Mode Selection
(Parallel control)
0
1
2
1
5
F_016
Set Drive’s No. for
Parallel Control
0
0
0
0
0
F_017
Maximum Output Frequency
60.0
60.0
60.0
50.0
60.0
F_018
Reference Frequency of
Accel/Decel Time
60.00
60.00
60.0
50.00
60.00
F_019
Primary Acceleration Time
5.0
3.0
3.0
3.0
1.0
F_020
Primary Deceleration Time
5.0
3.0
3.0
3.0
1.0
F_021
Launch Detection Time
(Parallel Control)
6.0
6.0
6.0
6.0
6.0
F_022
Launch Detection Level
(Parallel Control)
0.4
0.4
0.4
0.4
0.4
F_023
Cut-off Frequency
(Parallel Control)
50.0
50.0
50.0
42.0
50.0