Technical description of the burner
4.3 Technical data
Tab. B
(1)
Reference conditions: Ambient temperature 20°C - Barometric pressure 1013 mbar -Altitude 0m a.s.l. (H
i = 11.86 kWh/kg)
(2)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum output. The sound power
is measured with the “Free Field” method, as per EN 15036, and according to an accurate “Accuracy: Category 3” measurement, as described in
EN ISO 3746.
4.4 Electrical data
Tab. C
4.5 Burner equipment
RG2 - RG3 burners
Flange with insulating gasket .............................................. No. 1
Screw and nuts for flange ................................................... No. 1
Remote reset connection .................................................... No. 1
Screws and nuts for fixing the flange to the boiler .............. No. 4
Flexible hoses with nipples ................................................. No. 2
Installer booklet................................................................... No. 1
Spare Parts List................................................................... No. 1
Remote reset kit
The burner has a remote reset kit (RS) consisting of a connection
and a push-button operating at a distance of 20 metres max.
In order to install it, remove the safety lockout device installed at
the factory and insert the lockout supplied with the burner (see
electrical diagram).
RG1F TL - RG2F TL burners
Flange with insulating gasket .............................................. No. 1
Screw and nuts for flange.................................................... No. 1
Screws and nuts for fixing the flange to the boiler............... No. 4
7 pin plug............................................................................. No. 1
Flexible hoses with nipples.................................................. No. 2
Installer booklet ................................................................... No. 1
Spare Parts List................................................................... No. 1
Model RG2 RG3 RG1F TL RG2F TL
Delivery
(1)
Thermal power
(1)
kg/h
kW
4 10
47 119
7 15
83 178
2.7 5
32 60
4 10
47 119
Fuel
Light oil, viscosity 4 6 mm
2
/s at 20°C
Operation Intermittent (FS1)
Use Boilers: water and diathermic oil
Ambient temperature °C 0 - 40
Combustion air temperature °C max 40
Pump bar
Pressure: 8 15
Noise levels
(2)
Sound pressure
Sound power
dB (A)
61
72
64
75
60
71
61
72
Burner weight kg 13 15 13 13
Model RG2 RG3 RG1F TL RG2F TL
Power supply Single-phase, ~50Hz
230V ± 10%
Single phase, ~ 50-60Hz
220/230V ± 10%
Motor A
rpm
rad/s
0.9
2750
289
1.8
2800
294
0.9
2750
289
0.9
3300
347
0.9
2750
289
1
3135
329
Capacitor F 4 6.3 4 4
Ignition transformer Secondary 18 kV - 25 mA
Absorbed electrical power kW 0.18 0.39 0.155
(50Hz)
0.200
(60Hz)
0.165
(50Hz)
0.220
(60Hz)
Protection level IP 40