Rockwell Automation Publication 1715-UM001J-EN-P - December 2020 259
Appendix B 1715-IB16D Digital Input Module Diagnostics
Full Diagnostics Configuration
Selecting Full in the Diagnostics pull-down menu loads a set of threshold
default values into the threshold settings. This must be selected if an EOL is
used.
Figure 76 - Full Diagnostics Threshold Default Values
For a full-diagnostics setting configuration, use these resistor values.
None Diagnostics Configuration
Selecting None in the Diagnostics pull-down menu loads another set of default
values into the threshold settings. This is selected when no EOL devices are
used.
Figure 77 - None Diagnostics Threshold Default Values
Based on these settings, if the switch is closed, the input reports an ‘on’
condition anytime the voltage is above ~14.5V, but does not report a short
circuit, because there is no way to get the voltage to rise to 32V.
IMPORTANT
These are the most common commercially available EOL devices.
Table 59 - Full Diagnostics Resistor Values
Item Value
R1 15 k(1%) - power 0.5 W (max power dissipated 0.128 W)
R2 3.9 k(1%) - power 0.5 W (max power dissipated 0.128 W)
Loop supply voltage= 24V DC (±10%)