Programming and Parameters 1-47
UTILITY
Faults
241 [Fault Clear Mode]
Enables/disables a fault reset (clear
faults) attempt from any source. This
does not apply to fault codes which are
cleared indirectly via other actions.
Default:
Options:
1
0
1
“Enabled”
“Disabled”
“Enabled”
242 [Power Up Marker]
Elapsed hours since initial drive power
up. This value will rollover to 0 after the
drive has been powered on for more than
the max value shown. For relevance to
most recent power up see [Fault x Time].
Default:
Min/Max:
Units:
Read Only
0.0000/429496.7295 Hr
0.0/429496.7 Hr
0.0000/214748.3647 Hr
0.0001 Hr
0.1 Hr
244
246
248
250
252
254
256
258
243
245
247
249
251
253
255
257
[Fault 1 Code]
[Fault 2 Code]
[Fault 3 Code]
[Fault 4 Code]
[Fault 5 Code]
[Fault 6 Code]
[Fault 7 Code]
[Fault 8 Code]
A code that represents the fault that
tripped the drive. The codes will appear
in these parameters in the order they
occur ([Fault 1 Code] = the most recent
fault).
Default:
Min/Max:
Units:
Read Only
0/65535
0
244
246
248
250
252
254
256
258
[Fault 1 Time]
[Fault 2 Time]
[Fault 3 Time]
[Fault 4 Time]
[Fault 5 Time]
[Fault 6 Time]
[Fault 7 Time]
[Fault 8 Time]
The time between initial drive power up
and the occurrence of the associated trip
fault. Can be compared to [Power Up
Marker] for the time from the most recent
power up.
[Fault x Time] – [Power Up Marker] =
Time difference to the most recent power
up. A negative value indicates fault
occurred before most recent power up. A
positive value indicates fault occurred
after most recent power up.
Default:
Min/Max:
Units:
Read Only
0.0000/429496.7295 Hr
0.0000/214748.3647 Hr
0.0001 Hr
242
File
Group
No.
Parameter Name & Description
See page 1-2 for symbol descriptions
Values
Related
20B-UM001.book Page 47 Thursday, June 20, 2013 1:55 PM