2-16 Troubleshooting
Select testpoint with [Testpoint x Sel], parameters 234/236. Values can
be viewed with [Testpoint x Data], parameters 235/237.
Testpoint Codes and Functions
No.
(1)
(1)
Enter in [Testpoint x Sel].
Description Units
Values
Minimum Maximum Default
01 DPI Error Status 1 0 255 0
02 Heatsink Temp 0.1 degC –100.0 100.0 0
03 Active Cur Limit 1 0 32767 0
04 Active PWM Freq 1 Hz 2 10 4
05 Life MegaWatt Hr
(2)
(2)
Use the equation below to calculate total Lifetime MegaWatt Hours.
0.0001 MWh 0 214748.3647 0
06 Life Run Time 0.0001 Hrs 0 214748.3647 0
07 Life Pwr Up Time 0.0001 Hrs 0 214748.3647 0
08 Life Pwr Cycles 1 0 4294967295 0
09 Life MW-HR Fract
(2)
1 0 4294967295 0
10 MW-HR Frac Unit
(2)
1 0 4294967295 0
11 MCB Life Time 0.0001 Hrs 0 214748.3647 0
12 Raw Analog In 1 1 0 0
13 Raw Analog In 2 1 0 0
16 CS Msg Rx Cnt 1 0 65535 0
17 CS Msg Tx Cnt 1 0 65535 0
18 CS Timeout Cnt 1 0 255 0
19 CS Msg Bad Cnt 1 0 255 0
22 PC Msg Rx Cnt 1 0 65535 0
23 PC Msg Tx Cnt 1 0 65535 0
24-29 PC1-6 Timeout Cnt 1 0 255 0
30 CAN BusOff Cnt 1 0 65535 0
31 No. of Analog Inputs 1 0 x 0
32 Raw Temperature 1 0 65535 0
33 MTO Norm Mtr Amp 0.1 Amps 0 65535 0
34 DTO-Cmd Frequency 1 0 420 0
35 DTO-Cmd Cur Lim 0.1 0 0
36 DTO-Cmd DC Hold 1 0 32767 0
37 Control Bd Temp 0.1 0.0 60.0 0.0
Value of Code 9
Value of Code 10
---------------------------------
0.1×
⎝⎠
⎛⎞
Value of Code 5+ Total Lifetime MegaWatt Hours=