EasyManuals Logo
Home>Rockwell Automation>DC Drives>PowerFlex 755TM

Rockwell Automation PowerFlex 755TM User Manual

Rockwell Automation PowerFlex 755TM
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #65 background imageLoading...
Page #65 background image
Rockwell Automation Publication DRIVES-AT005D-EN-P - May 2022 65
Appendix A Electrical Ratings, Recommended Protective Devices, and DC Bus Capacitance
Table 8 - PowerFlex 755TM Non-regenerative Supply – Single and Dual Density, 400V AC (540V DC Output)
Cat.No
20JEH... Module Size
(1)
(1) Modules are available in single density and dual density. Modules can be paralleled to increase the rating. In this table ‘1X’ means one single-density module, ‘2X’ means one dual-density module. See
Paralleling PowerFlex 755TM Non-regenerative Modules on page 41 for more information.
DC Output Rating
(1)
Internal Optional DC
Bus Capacitance (uF)
(2)
(2) For paralleled modules, sum the corresponding 1X and 2X internal optional capacitance values to obtain the overall bus supply internal/optional DC bus capacitance value.
Power (kW)
Cont.
AmpsND HD
C770 1X
479 - 887
15,000
-400740
C1K4 2X
910 - 1685
30,000
-7311354
20-750-MN…
(3)
(3) Parallel configurations are built-up from separate enclosures and 20-750-MN… single-density 1X and dual-density 2X roll-in modules. See the PowerFlex 755TM IP00 Open Type Kits Technical Data,
publication 750-TD101.
1X/2X
1341 - 2484
Total internal uF values
calculated based on
module size and quantity
of parallel modules
-11192072
2X/2X 1771 - 3282
-14792738
1X/2X/2X 2203 - 4080
- 1886 3493
2X/2X/2X 2634 - 4879
-21984070
1X/1X/ 2634 - 4879
2X/x2X - 2198 4070
2X/2X/ 3497 - 6475
2X/2X - 2917 5402
1X/1X/ 4359 - 8072
2X/2X/2X/2X - 3636 6734
2X/2X/2X/2X/2X/2X
(4)
(4) The ratings for the configurations in these rows can only be achieved by using customer-sourced bus bars.
5221 - 9668
-43568066
Cat.No.
20JEH… Module Size
(1)
Maximum DC Bus Capacitance (uF)
(5)(6)
(5) For paralleled modules, sum the corresponding 1X and 2X maximum external capacitance values to obtain the overall bus supply system maximum external DC bus capacitance value.
(6) Select the fastest precharge ramp time that supports the total connected DC bus capacitance. Perform calculations to determine the required DC bus capacitance and the system total DC bus
capacitance. See DC Bus Capacitance Calculation Method on page 87.
Precharge
Ramp
Precharge
Ramp
Precharge
Ramp
Precharge
Ramp
Precharge
Ramp
Precharge
Ramp
Precharge
Ramp
Precharge
Ramp
0.2 s 1.3 s 2.0 s 5.0 s 10 s 20 s 30 s 60 s
C770 1X 81,700 408,500 817,000 2,042,500 4,085,000 8,170,000 12,255,000 24,510,000
C1K4 2X 150,700 753,500 1,507,000 3,767,500 7,535,000 15,070,000 22,605,000 45,210,000

Table of Contents

Questions and Answers: