78 Rockwell Automation Publication DRIVES-AT005D-EN-P - May 2022
Appendix A Electrical Ratings, Recommended Protective Devices, and DC Bus Capacitance
Table 17 - PowerFlex 755TM Non-regenerative Supplies – Single and Dual Density, 600V AC (810V DC Output)
Cat.No
20JEH... Module Size
(1)
(1) Modules are available in single density (S) and dual density (D). Modules can be paralleled to
increase the rating. In this table, ‘1X’ means a single-density module, ‘2X’ means a dual-density
module. See Paralleling PowerFlex 755TM Non-regenerative Modules on page 41
.
DC Output Rating
(1)
Internal Optional DC
Bus Capacitance (uF)
(2)
(2) For paralleled modules sum the corresponding 1X and 2X maximum internal optional capacitance
values to obtain the overall bus supply internal/optional DC bus capacitance value.
kW Rating
Cont.
Amps
ND HD
E545 1X
488 - 602
7,000
-403497
E980 2X
876 1082
14,000
-738911
20-750-
MN…
(3)
(3) Parallel configurations are built-up from separate enclosures and 20-750-MN… single-density 1X
and dual-density 2X roll-in modules. See the PowerFlex 755TM IP00 Open Type Kits Technical Data,
publication 750-TD101.
1X/2X
1365 - 1686
Total internal uF values
calculated based on
module size and quantity
of parallel modules
- 1127 1392
2X/2X
1804 - 2227
-14901839
1X/2X/2X
2243 - 2769
-18522286
2X/2X/2X
2682 - 3311
-22142734
1X/1X/ 2682 - 3311
2X/x2X - 2214 2734
2X/2X/ 3560 - 4395
2X/2X - 2939 3628
1X/1X/ 4437 - 5478
2X/2X/2X/2X - 3663 4523
2X/2X/2X/2X/2X/2X
5315 - 6562
-43885417
Cat.No.
20JEH…
Module
Size
(1)
(1) Modules are available in single density and dual density. Modules can be paralleled to increase the rating. In this table ‘1X’ means one single-density module, ‘2X’ means
one dual-density module. See Paralleling PowerFlex 755TM Non-regenerative Modules on page 41 for more information.
Maximum DC Bus Capacitance (uF)
(2)
(3)
(2) For paralleled modules, sum the corresponding 1X and 2X maximum external capacitance values to obtain the overall bus supply system maximum external DC bus
capacitance value.
(3) Select the fastest precharge ramp time that supports the total connected DC bus capacitance. Perform calculations to determine the required DC bus capacitance and
the system total DC bus capacitance. See DC Bus Capacitance Calculation Method on page 87
.
Precharge
Ramp
Precharge
Ramp
Precharge
Ramp
Precharge
Ramp
Precharge
Ramp
Precharge
Ramp
Precharge
Ramp
Precharge
Ramp
0.2 s 1.3 s 2.0 s 5.0 s 10 s 20 s 30 s 60 s
E545 1X 27,800 139,000 278,000 695,000 1,390,000 2,780,000 4,170,000 8,340,000
E980 2X 50,700 253,500 507,000 1,267,500 2,535,000 5,070,000 7,605,000 15,210,000

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 755TM and is the answer not in the manual?

Rockwell Automation PowerFlex 755TM Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 755TM
CategoryDC Drives
LanguageEnglish

Related product manuals