Programming and Parameters 3-33
DYNAMIC CONTROL (File D)
Restart Modes
167 [Powerup Delay]
Defines the programmed delay time, in
seconds, before a start command is
accepted after a power up.
Default:
Min/Max:
Units:
0.0 Secs
0.0/30.0 Secs
0.1 Secs
168 [Start At PowerUp]
Enables/disables a feature to issue a Start
or Run command and automatically
resume running at commanded speed
after drive input power is restored.
Requires a digital input configured for Run
or Start and a valid start contact.
Default:
Options:
0
0
1
“Disabled”
“Disabled”
“Enabled”
169 [Flying Start En]
Enables/disables the function which
reconnects to a spinning motor at actual
RPM when a start command is issued.
Default:
Options:
0
0
1
“Disabled”
“Disabled”
“Enabled”
170
170 [Flying StartGain]
Sets the response of the flying start
function.
Default:
Min/Max:
Units:
4000
20/32767
1
169
174 [Auto Rstrt Tries]
Sets the maximum number of times the
drive attempts to reset a fault and restart.
Default:
Min/Max:
Units:
0
0/9
1
175
175 [Auto Rstrt Delay]
Sets the time between restart attempts
when [Auto Rstrt Tries] is set to a value
other than zero.
Default:
Min/Max:
Units:
1.0 Secs
0.5/30.0 Secs
0.1 Secs
174
File D
Group
No.
Parameter Name and Description
See page 3-2 for symbol descriptions
Values
Related
E C
!
ATTENTION: Equipment damage and/or personal injury may
result if this parameter is used in an inappropriate application. Do
not use this function without considering applicable local, national
and international codes, standards, regulations or industry
guidelines.
!
ATTENTION: Equipment damage and/or personal injury may
result if this parameter is used in an inappropriate application. Do
not use this function without considering applicable local, national
and international codes, standards, regulations or industry
guidelines.