EasyManua.ls Logo

Rosemount Analytical 54C - Input Power Selection

Rosemount Analytical 54C
53 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-5
MODEL 54 C SECTION 1
INSTALLATION
CAUTION
DO NOT apply power to the instrument
until all electrical connections are verified
and secure. AC connections and groun-
ding must be in compliance with UL 508
and/or local electrical code.
NOTE
For best EMI/RFI protection the output
cable should be shielded and enclosed in
an earth grounded rigid metal conduit.
Connect the cable’s outer shield to either
earth ground terminal on TB2, Figur
e 1-7.
The sensor cable should also be shielded.
Connect the outer shield to earth ground
via terminal 1 of TB1, Figure 1-7 If the outer
shield is braided an appropriate metal
cable gland fitting may be used to connect
the outer braid to earth ground via the
instrument.
NOTE
The user must provide a means to discon-
nect the main power supply in the form of cir-
cuit breaker or switch. The circuit breaker or
the switch must be located in close proximity
to the instrument and identified as the dis-
connecting device for the instrument.
NOTE
HART
®
communications not available.
Current output 1 switch must be in single
loop position. See Figur
e 1-7.
1.3.1 Analyzer Wiring. Figure 1-7, Figure 1-8 and
Figur
e 1-9 show how the analyzer should be wired.
A. Connect power input and output wiring per
Figur
e 1-7.
B. Wire inductive (Toroidal) sensors per Figur
e 1-9 or
wire contacting sensor per Figure 1-8.
NOTE
Do not allow earth ground (TB 1-1) to short
(contact) TB 1-2 inner drain, if this occurs
a ground loop may give inaccurate con-
ductivity readings.
1.3.2 Input Power Selection (Code -08). The Model
54C -08 is field selectable for 115Vac or 230Vac
50/60Hz. Refer to Drawing Number 400054C06.
FIGURE 1-6. Conduit Openings