6-11
Options
ALARM
The digital and analog outputs are in alarm. Possible causes of this
condition include, but are not limited to, an electronics failure or an
open sensor. This message is displayed on the Process Variable line and
is always accompanied by a more descriptive message on the Process
Variable Unit line. In the case of a Sensor 1 failure , for example, the
Process Variable line displays “ALARM,” and the Process Variable Unit
line alternates between “SNSR 1” and “FAIL.”
WARN
The transmitter is still operating, but something is not correct. Possible
causes of this condition include, but are not limited to, an out-of-range
sensor, a fixed loop, or an open sensor condition. In the case of a
Sensor 2 failure with Hot Backup enabled, the Process Variable line
displays “WARN,” and the Process Variable Unit line alternates
between “SNSR 2” and “RANGE.”
The device sometimes requires further interrogation to determine the
source of the warning. Contact Rosemount Customer Central at
(800) 999-9307 for technical support.