EasyManuals Logo

Saftronics HPVFE User Manual

Saftronics HPVFE
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #58 background imageLoading...
Page #58 background image
Advanced Program Group (continued)
57
A436 [Compensation]
Enables/disables correction options that may improve problems with motor instability.
Options
0
“Disabled”
1
“Electrical” (Default)
Some drive/motor combinations have inherent instabilities which are exhibited as
non-sinusodial motor currents. This setting attempts to correct this condition.
2
“Mechanical” Some motor/load combinations have mechanical resonances which can be excited by
the drive current regulator. This setting slows down the current regulator response and
attempts to correct this condition.
3
“Both”
A437 [Slip Hertz @ FLA]
Related Parameter(s): P103
Compensates for the inherent slip in an induction motor. This frequency is added to the commanded output frequency based on motor current.
Values
Default
2.0 Hz
Min/Max:
0.0/ 10.0 Hz
Display:
0.1 Hz
A438 [Process Time Lo]
Related Parameter(s): d010, P104
Scales the time value when the drive is running at P104 [Minimum Freq]. When set to a value other than zero, d010 [Process Display] indicates
the duration of the process.
Values
Default
0.00
Min/Max:
0.00/ 99.99
Display:
0.01
A439 [Process Time Hi]
Related Parameter(s): d010, P105
Scales the time value when the drive is running at P105 [Maximum Freq]. When set to a value other than zero, d010 [Process Display]
indicates the duration of the process.
Values
Default
0.00
Min/Max:
0.00/ 99.99
Display:
0.01

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Saftronics HPVFE and is the answer not in the manual?

Saftronics HPVFE Specifications

General IconGeneral
BrandSaftronics
ModelHPVFE
CategoryDC Drives
LanguageEnglish

Related product manuals