Advanced Program Group (continued)
58
A440 [Process Factor]
Related Parameter(s): d010
Scales the value displayed by d010 [Process Display].
Output Freq
x
Process Factor
=
Process Display
Values
Default
30.0
Min/Max:
0.1/999.9
Display:
0.1
A441 [Bus Reg Mode]
Controls the operation of the drive voltage regulation, which is normally operational at deceleration or when the bus voltage rises.
Refer to the Attention statement on page P-3 for important information on bus regulation.
Values
0
“Disabled”
1
“Enabled” (Default)
A442 [Current Limit]
Maximum output current allowed before current limiting occurs.
Values
Default
Drive Rated Amps x 1.5
Min/Max:
0.1/(Drive Rated Amps x 1.8)
Display:
0.1 Amps
A444 [Motor OL Select]
Related Parameter(s): P102, P103
Drive provides Class 10 motor overload protection. Settings 0-2 select the derating factor for the I
2
t overload function.
Options
0
“No Derate” (Default)
1
“Min
Derate
2
“Max Derate