53 Fan Coil FC600 Instruction Manual
Parameter
number
Type of setting Description Default
Values
d04 Heat and Cool mode
selection - This
parameter is available
only when d01 = 0
(2 pipe) and d02 =
0 or 2 ( S1-COM no
function, or pipe
sensor connected)
0 = Heating & Cooling available using MODE button
1 = Cooling ONLY (user can’t change mode using MODE
button)
2 = Heating ONLY (user can’t change mode using MODE
button)
1
d 05 Offset
This functions allows you to calibrate your displayed
temperature value. It can be adjusted from -3.0 ⁰C to +3.0⁰C
0⁰C
d06 Max heating setpoint From 5⁰C to 40 ⁰C 40 ⁰C
d07 Min heating setpoint From 5⁰C to 40 ⁰C 5⁰C
d08 Max cooling setpoint
temperature
From 5⁰C to 40 ⁰C 40 ⁰C
d09 Min cooling setpoint
temperature
From 5⁰C to 40 ⁰C 5⁰C
d10 ECO set point in
Heating mode
This setting is responsible for the ECO setpoint
temperature when the thermostat is in Heating mode.
Can be set to any value from 5⁰C to 40 ⁰C.
15⁰C
d11 ECO set point in
Cooling mode
This setting is responsible for the ECO setpoint
temperature when the thermostat is in Cooling mode.
Can be set to any value from 5⁰C to 40 ⁰C.
30⁰C
d12 Time zone From -13 to +13 +1
d13 DST – Day light
saving time
0 = Enabled
1 = Disabled
0
d14 Key lock function Use this function to enable/disable auto keylock function.
0 = manual - the user can lock the keys manually via
device or App.
1 = Auto (thermostat will lock the keys after 5 minutes
since last button press)
2 = Unlocked the user can't lock the keys.
0
d 15 TPI/Span control 0 = TPI
1 = Span control
0
d 16 Set the control type
in modulation. This
parameter is available
only if we select TPI
algorithm, not SPAN
0 = Slow change environment
1 = Fast change environment
0