EasyManua.ls Logo

Samson 3725 series - Attachment to Control Valve and Accessories

Samson 3725 series
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 Attachment to the control
valve – Mounting parts and
accessories
WARNING!
Attach the positioner, keeping the following
sequence:
1. Mount the positioner on the control valve
2. Connect the supply air
3. Connect the electrical power
4. Perform the start-up settings
The positioner is suitable for the following
types of attachment:
4
Direct attachment to SAMSON
Type 3277 Actuator
4
Attachment to actuators according to
IEC 60534-6 (NAMUR)
4
Attachment to Type 3372 Linear Actua-
tor (V2001 Valve Series)
4
Attachment to rotary actuators according
to VDI/VDE 3845
NOTICE
Attach the positioner to the control valve,
observing the following instructions to avoid
damaging the positioner.
Use only the mounting parts/accessories
listed in the table (section 4.5). Observe
the type of attachment!
Observe the assignment between lever
and pin position!
Lever and pin position
The positioner is adapted to the actuator
and to the rated travel by the lever on the
back of the positioner and the pin inserted
into the lever.
The travel tables show the maximum adjust-
ment range at the positioner. The travel that
can be implemented at the valve is addition-
ally restricted by the selected fail-safe posi-
tion and the required compression of the ac-
tuator springs.
The positioner is standard equipped with the
lever M (pin position 35).
NOTICE
When undoing the lever, e.g. with a screw-
driver, do not move the shaft by moving the
lever past the mechanical stops. Otherwise,
the internal stops may be damaged.
12 EB 8394 EN
Attachment to the control valve Mounting parts and accessories
Fig. 3 · Lever M with pin position 35
Fig. 4 · Stop for lever

Related product manuals