system deviation between the manual and
automatic set point while manually moving
the valve in Code
P17
.
The manual set point is adjusted in steps of
0.1 %. You can move the valve controlled
within its range.
Positioner that has not been initialized
Keep or pressed to move the valve
manually.
The valve is only moved in one direction un-
controlled. The bar elements on the display
indicate the change in direction.
Press to deactivate the manual adjust-
ment function.
Note: The
Manual mode
function can only
be exited as described. The positioner does
not automatically exit this function and re-
turn to the display with status indication.
7.11 Reset
The positioner is in closed-loop operation
after the initialization has been successfully
completed.
A reset causes an initialization to be can-
celed and all parameters settings are reset to
the default settings (refer to the code list in
section 8).
Enable configuration (refer to section 7.1).
Press or until Code
P18
appears.
Press for six seconds, the display counts
down
6-5-4-3-2-1.
RST
blinks.
After the positioner has been reset, the dis-
play automatically returns to status indica-
tion (P0). In this display, the angle is indi-
cated in degree relative to the longitudinal
axis.
EB 8394 EN 41
Start-up – Settings