7.7 Setting other parameters
The following table lists all the parameter
codes and their default settings.
If you want to change the default setting of a
parameter, proceed in the same manner as
previously described.
Note: The selected parameter code remains
active until you change the setting or exit the
parameter code.
More details concerning the parameter
codes can be found in section 8.
EB 8394 EN 37
Start-up – Settings
Parameter codes
Codes marked with * can be changed without having to re-initialize the positioner
[...] Default setting
P0
Display with status indication
P11
End position w > [OFF]
P1
Reading direction
P14
Display of reference variable w
P2
* Fail-safe position [ATO]
P15
INIT Start initialization
P3
* Pin position [35]
P16
ZERO Start zero calibration
P4
* Nominal range [MAX]
P17
Manual mode
P5
Characteristic [1]
P18
Reset
P6
Reference variable [4 to 20 mA]
P19
Enable configuration
P7
w/x direction of action [>>]
P20
Read firmware
P8*
Gain Kp [50]
P9
* Pressure limit 2.4 bar [OFF]
P10
End position w < [ON]