P6
*
Reference variable
[4...20 mA]
SRLO/SRHI
For split-range operation
SRLO
– low range 4 to 11.9 mA
SRHI
– high range 12.1 to 20 mA
P7 *
w/x
[>>] /<>
Direction of action of the reference variable w to the travel/rota-
tional angle x (increasing/increasing or increasing/decreasing).
P8
Gain K
P
30/[50]
On initializing the positioner, the gain is set to the selected value.
If the positioner hunts, the Kp value can be reduced. The positioner
must be then re-initialized afterwards.
P9
*
Pressure limit
ON/[OFF]
The signal pressure can take on the same pressure as the supply air
at the maximum [
OFF
] or, in the case that the maximum actuator
force can damage the valve, the pressure is limited to approx.
2.4 bar.
P10
*
End position w <
[ON]/OFF
Lower tight-closing function:
If w reaches up to 1 % towards the final value that causes the valve
to close, the actuator is immediately completely vented (with
ATO
-
Air to open) or filled with air (with
ATC
- Air to close).
P11
*
End position w >
ON/[OFF]
Upper tight-closing function:
If w reaches up to 99 % towards the final value that causes the valve
to open, the actuator is immediately completely filled with air (with
ATO
- Air to open) or vented (with
ATC
- Air to close).
P14
Info w Initialized
Not initialized
Indicates the internally adjusted set point (adjusted set point in 0 to
100 % according to the settings in P6 and P7).
Press to display external set point (applied set point in 0 to
100 % according to the 4-20 mA signal).
Displays external set point in 0 to 100 % according to the 4-20 mA
signal.
P15
Start
initialization
The initialization process can be interrupted by pressing .
The control valve moves to its fail-safe position
After a power supply failure during initialization, the positioner
starts with the settings from the last initialization (if possible).
P16 *
Start
zero calibration
The zero calibration process can be interrupted by pressing . The
positioner returns to closed-loop operation.
Note: A zero calibration cannot be started when error code E1 ex-
ists.
After a power supply failure during zero calibration, the positioner
starts with the settings from the last zero calibration.
P17
Manual mode Press or to enter set point.
44 EB 8394 EN
Code list