E5
Standstill detection is
not possible
(initialization error)
Supply pressure is too low or varies. Mounting incorrect.
Recommended action Check supply air and positioner mounting.
Re-initialize the positioner.
E6
Travel is not achieved
during initialization
(initialization error)
Supply pressure is too low, actuator leaks, incorrect travel adjusted
or pressure limit function activated.
Recommended action Check supply air, positioner mounting and setting.
Re-initialize the positioner.
E7
Actuator does not move
(initialization error)
No supply air, mounting blocked.
No input signal or input signal below 3.7 mA
Recommended action Check supply air, positioner mounting and mA input signal.
Re-initialize the positioner.
E8
Travel signal
at lower/upper limit
Wrong pin position, wrong lever, wrong attachment direction when
NAMUR attachment is used.
Recommended action Reset error code (see section 7.12).
Check positioner mounting and re-initialize the positioner.
E9
Software Internal software error
Return positioner to SAMSON AG for repair.
E10
to
E15
Hardware Internal device error
Recommended action Return positioner to SAMSON AG for repair.
46 EB 8394 EN