EB 8384-1 EN 21
Design and principle of operation
3.4 Travel tables
The M lever is included in the scope of delivery.
S, L, XL levers for attachment according to IEC60534-6 (NAMUR) are available as
accessories (see Table5 on page19). The XXL lever is available on request.
Table9: Direct attachment to Type3277-5 and Type3277 Actuator
Actuator size Rated travel
Adjustment range at
positioner
Required
lever
Assigned pin
position[cm²] [mm] Travel[mm]
120 7.5 5.0 to 16.0 M 25
120/175/240/350 15 7.0 to 22.0 M 35
355/700/750 30 10.0 to 32.0 M 50
Table10: Attachment according to IEC60534-6 (NAMUR)
SAMSON valves with Type3271 Actuator Other valves/actuators
Required lever
Assigned pin
position
Actuator area Rated travel Min. travel Max. travel
[cm²] [mm] [mm] [mm]
60 and 120
withType3510Valve
7.5 3.5 11.0 S 17
120 7.5 5.0 16.0 M 25
120/175/240/350 15
7.0 22.0 M 35
355/700/750 7.5
355/700/750 15 and 30 10.0 32.0 M 50
1000/1400/2800
30 14.0 44.0 L 70
60 20.0 64.0 L 100
1400/2800 120 40.0 128.0 XL 200
See manufacturer's
specications
200 Seemanufacturer'sspecications 300
Table11: Attachment to rotary actuators
Opening angle Required lever Assigned pin position
20to100° M 90°
Note