EB 8384-1 EN 7
Safety instructions and measures
Personal protective equipment
No personal protective equipment is required for the direct handling of the positioner. Work
on the control valve may be necessary when mounting or removing the device.
Î Observetherequirementsforpersonalprotectiveequipmentspeciedinthevalvedocu-
mentation.
Î Check with the plant operator for details on further protective equipment.
Revisions and other modications
Revisions,conversionsorothermodicationsoftheproductarenotauthorizedbySAMSON.
They are performed at the user's own risk and may lead to safety hazards, for example. Fur-
thermore, the product may no longer meet the requirements for its intended use.
Safety features
Upon failure of the air supply or electric signal, the positioner vents the actuator, causing the
valve to move to the fail-safe position determined by the actuator.
Warning against residual hazards
Thepositionerhasdirectinuenceonthecontrolvalve.Anyhazardsthatcouldbecausedin
the valve by the process medium, the signal pressure or by moving parts are to be prevented
by taking appropriate precautions. They must observe all hazard statements, warning and
caution notes in these mounting and operating instructions, especially for installation, start-
up and service work.
If inadmissible motions or forces are produced in the pneumatic actuator as a result of the
supply pressure level, it must be restricted using a suitable supply pressure reducing station.
Explosion protection
Explosivedustatmospheresofzone21orzone22
ThefollowingappliestotypeofprotectionExiincombustibledustatmospheres:
Ifintrinsicsafetyisimpairedbytheinuenceofdust,anenclosurecomplyingwith
Clause6.1.3ofEN60079-11withatleastindegreeofprotectionIP5Xmustbeused.
TherequirementsaccordingtoClause6.1.3applytothecableglandsaccordingly.The
degreeofingressprotectionisveriedbyatestaccordingtoIEC60529andEN60079-
0 (e.g. performed by VDE).
For use in the presence of combustible dust in compliance with type of protection
ExtbIIIC(protectionbyenclosure),observeClause5.6.3ofEN60079-14.

Table of Contents

Other manuals for Samson 3730-1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samson 3730-1 and is the answer not in the manual?

Samson 3730-1 Specifications

General IconGeneral
Supply air pressure1.4 to 7 bar (20 to 100 psi)
Housing materialAluminum
Protection classIP 65
Output SignalPneumatic
Pressure RangeUp to 7 bar (100 psi)
Port SizeG1/4 or 1/4" NPT
MaterialAluminum
Accuracy±1% of span