EasyManua.ls Logo

Samson 3730-1 - Page 86

Samson 3730-1
112 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
86 EB 8384-1 EN
Appendix
Error codes
E6 Travel is not achieved
during initialization
Supply pressure is too low, actuator leaks, incorrect travel adjusted
or pressure limit function activated.
Recommended action Check supply air, positioner mounting and setting.
Re-initialize the positioner.
E7 Actuator does not move No supply air, mounting blocked.
Noinputsignalorinputsignalbelow3.7mA
Recommended action Check supply air, positioner mounting and mA input signal.
Re-initialize the positioner.
E8 Travel signal at lower/
upper limit
Wrong pin position, wrong lever, wrong attachment direction when
NAMUR attachment is used.
Recommended action Check positioner mounting and re-initialize the positioner.
E9 Internal error Switch off positioner and wait ten seconds before switching it on
again.Iftheerrorreappears,returnpositionertoSAMSONAG
for repair.
E10
to
E13
Device error (internal) ReturnpositionertoSAMSONAGforrepair.
E14 Data error Resetpositioner(P18).Recongureandre-initializethepositioner.
Iftheerrorreappears,returnpositionertoSAMSONAGforre-
pair.
E15 Device error (internal) ReturnpositionertoSAMSONAGforrepair.

Table of Contents

Other manuals for Samson 3730-1

Related product manuals