5-2 EB 8355-2 EN
Installation
Proceedasfollows:
ÃŽ Lay out the necessary material and tools
tohavethemreadyduringmounting.
ÃŽ Determine the operating direction of the
positioner control loop (see sec-
tion5.2.1).
ÃŽ Remove the protective cover on the back
of the positioner.
ÃŽ Remove the protective caps from the
pneumatic connections.
5.2.1 Determining the
operating direction of
the positioner control
loop
Operating direction increasing/increasing
<<
− The signal pressure p
st
rises as the input
signal p
e
(set point) rises
− The signal pressure p
st
decreases as the
input signal p
e
(set point) decreases
Operating direction increasing/decreasing
<>
− The signal pressure p
st
decreases as the
input signal p
e
(set point) rises
− The signal pressure p
st
rises as the input
signal p
e
(set point) decreases
Ontheturnboard(7),theoperatingdirection
is indicated by symbols (direct <<, reverse
<>).Dependingonthepositionoftheturn-
board, the adjusted operating direction and
the associated symbol is visible. If the re-
quired operating direction does not corre-
spond to the visible symbol or if the operat-
ing direction is to be changed, proceed as
follows:
ÃŽ Unscrew the fastening screw from the
turnboard.
Î Turntheturnboardby180°.Makesure
that the three rubber gaskets inserted in
the housing remain in position.
ÃŽ Fasten the turnboard.
5.3 Positioner attachment
5.3.1 Direct attachment to
Type3277 Actuator
ÃŽ Required mounting parts and accesso-
ries:section5.8
Î See Fig.5-2
The positioner is mounted on the left or right
side of the valve depending on the actuator's
direction of action (fail-safe action) and the
operating direction of the positioner control
loop (see Fig.5-1, top).
1. Fasten the clamp (1.2) to the actuator
stem, making sure that the fastening
screw rests in the groove of the actuator
stem.
2. Fasten the associated pick-up lever D1 or
D2(with355/700cm²actuators)tothe
feedback lever of the positioner.
3. Secure the intermediate plate (15) with
the gasket facing towards the actuator
yoke.
SUPPLY
Actuator stem extends
Actuator stem retracts
Internal signal pres-
sure connection
Side view of connection block
Signal pressure
connection over piping
Connection block
Tip of gasket (16)
Operating
direction>>Left
attachment
Operating
direction<>Left
attachment
With gasket (new)
With switch plate (old)
Switch plate (13)
Gasket (16)
Cover
Switchover plate
Signal pressure input
Signal pressure
input for left
attachment
Seal with
lter
With right
attachment
Marking
Marking
Symbol
Actuator stem extends
Actuator stem retracts
Operating
direction<>Right
attachment
Actuator stem extends
>>Operatingdirection<>
Left attachment Right attachment
Actuator stem retracts
<>Operatingdirection>>
Left attachment Right attachment
Operating
direction>>Right
attachment
Fig.5-1: Mounting position and connection of signal pressure for Type3277 Actuator (top) and
Type3277-5 Actuator (120cm²) (bottom)