5-4 EB 8355-2 EN
Installation
4. Position the positioner such that the pick-
up lever slides in line over the pin (1.1)
of the clamp (1.2). Fasten the positioner
to the intermediate plate (15).
5. Mount cover (16).
6. Check whether the correct range spring
has been installed as listed in sec-
tion5.8.
Range spring 1 is installed as standard.
If necessary, replace it with range spring
2includedintheaccessoriesandxitat
the outer hook-in holes.
Actuators with 175 to 750cm² effective
areas
7. Make sure that the tip of the gasket (16)
projecting from the side of the connec-
tion block (Fig.5-1, middle) is positioned
to match the actuator symbol for the ac-
tuator's fail-safe action "actuator stem
extends" or "actuator stem retracts".
If this is not the case, unscrew the three
fastening screws and lift off the cover.
Turnthegasket(16)by180°andre-in-
sert it.
1.2
D2
D1
Ventplug
Ventplugmustpoint
downward when the
valve is installed
Viewontothesignalpressureconnection
Left attachment Right attachment
Cover
Switchover plate
Intermediate plate (15)
Clamp (1.2)
Signal pressure borehole
175to750cm²
120cm²
Type3277
Type3277-5
Fig.5-2: Mounting the clamp
Travel
789101112
6.1
4
6.2
2.1
3
2.2
5
1
1.1
1.2
P
e
9 Supply
V
P
st
Q
Xp
p
i
mA
13
4
6.1 6.2
3 7 8 9 11
Fig.5-3: Functional diagram and inside view