9-6 EB 8355-2 EN
Servicing
Table 9-1: Recommended inspection and testing
Inspection and testing Action to be taken in the event of a negative
result
Check the markings, labels and nameplates on
the positioner for their readability and complete-
ness.
Immediately renew damaged, missing or incor-
rect nameplates or labels.
Clean any inscriptions that are covered with dirt
and are illegible.
Check the positioner and leakage sensor (if
installed)toensuretheyaremountedrmly.
Tighten the any loose mounting screws.
Check the pneumatic connections. Tighten any loose male connectors of the screw
ttings.
Renew any air pipes or hoses that leak.
Check the power supply wires. Tighten any loose cable glands.
Make sure that the stranded wires are pushed into
the terminals and tighten any loose screws on the
the terminals.
Renew damaged lines.