Product Specifications
2-22 Samsung Electronics
Model
AVXDUH210EG
AVXDUH280EG
Power Supply ø/V/Hz 1/220~240/50
Mode *
1)
HP
Performance
Capacity
Cooling *
2)
kW 22.4 28.0
Btu/h 76,400 95,500
Heating *
3)
kW 25.0 31.5
Btu/h 85,300 107,400
Condensate (with High fan speed) Liters/h -
Power
Input W 1,000 (2 Motor)
Running Current A 5.2 (2 Motor)
Sound Level Sound Pressure (High/Low) *
4)
dB(A) 48.0
Fan
Type - Sirocco Fan
Motor
Model - OSME-4804SAC/4904SAC[S354/S355]
Type - Tap
Output W 460 (2 Motor)
Airflow Rate
Cooling (High)
m
3
/min
70.0
Heating (High) 74.0
Cooling (High)
CFM
2,472
Heating (High) 2,613
External Static
Pressure
Standard(Min.~Max) mmHO 0/8/20
Standard(Min.~Max) WG
-
Refrigerant
Type - R410A
Control Method - EEV
Temperature Control - Micom&Thermistors
Safety Devices - Fuse
Option Code - 015A00-160000 015A00-170000
Piping
Connections
Liquid (Flare) ø,mm 9.52
Gas (Flare) ø,mm 19.05(Connect Pipe:22.23)
Drain ø,mm ID 16.1/OD 21.7
Weight
Net Weight kg 101.4
Shipping Weight kg 114.4
Dimensions
Net Dimensions (W×H×D) mm 1,640x468x670
Shipping Dimensions (W×H×D) mm 2,015x542x812
Functions
Auto Restart - O
Auto change over - O
Auto Swing - X
Group/Individual Control - O
External Contact Control - O
Trouble Shooting by LED - X
Standard
Accessories
Installation Manual - O
Operation Manual - O
Pattern Sheet for Installation - X
Flexible Drain Hose - X
Filter / Safety Grille - Filter (Washable)
Drain Pump (Pumping speed / lift) - -
Wireless Remote Controller - -
Optional
Accessories
Wireless Remote Controller - MR-AH01
Duct Receiver Kits
Receiver - MRK-A00
Receiver Wire - MRW-10A
Wired Remote
Controller
Multi fuction - -
Premium - MWR-WS00*
Standard - MWR-TH01
Simplified - -
External Contact Interface Module - MIM-B14
Drain Pump -
-
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.
Indoor Unit(cont.)
QSUPER Duct
$9;&6+B$BaLQGG