installing the unit _27
ENGLISH
Piping examples
Branch with Y-joint
Branch with Y and Header joint
Branch with Header joint
One outdoor
unit installed
GF
h i j k l m n
b
a
c d e f g p
b
a
c d e f
g
h
i
Multiple
outdoor units
installed
GF
h i j k l m n
b
a
c d e f g p
Items Examples Remarks
Max.
piping
length
Outdoor
~
Indoor unit
Piping
( Equivalent
piping)
200m (656´)
220m (722´)
Branch with Y joint
a+b+c+d+e+f+g+p
200(220)m / 656(722)´
Equivalent pipe
length
Y-joint:0.5m,
Header:1m
Branch with Y joint and
Header joint
a+i+k200(220)m / 656(722)´
a+b+h200(220)m / 656(722)´
Branch with header joint a+i200(220)m / 656(722)´
Total piping
1000m (3281´)
Branch with Y joint
a+b+c+d+e+f+g+p+h+i+j+k+l+
m+n1000m / 3281´
Branch with Y joint and
Header joint
a+b+c+d+e+f+g+p+h+i+j+k
1000m / 3281´
Branch with Header joint
a+b+c+d+e+f+g+p+h+i
1000m / 3281´
Outdoor
~
Outdoor unit
Piping
10m (33´)
r
10 (33), s
10 (33), t
10 m (33´)
Equivalent
piping
13m (43´)
r
13 (43), s
13 (43), t
13 m (43´)
Level
difference
Outdoor ~
Indoor unit
Piping
50/40m
(164/131´)
H1
50m (164´) / 40 m (131´ )
Indoor ~ Indoor
unit
Piping
15m (49´)
H2
15 m (49´)
Outdoor ~
Outdoor unit
Piping
5m (16´)
H3
5 m (16´)
Allowable
length
after branch
The first branch
~
the farthest
indoor unit
Piping
45m (148´)
b+c+d+e+f+g+p
45 m(148´), i
45m(148´)
Piping
90m (295´)
It needs to satisfy required conditions
Only apply to
DVM PLUS III
Required condition Example
The first branch joint ~
the farthest indoor unit
If the sum of pipe length (b+c+d+e+f+g+p) is over 45m (148´), (but not exceed :
90m/295´) increase pipe size of b,c,d,e,f,g (b,c,d,e,f,g : pipe 1 size up)
Total piping
length
If main pipe size is not increased,
a+bx2+cx2+dx2+ex2+fx2+gx2+h+i+j+k+l+m+n+p1000 m (3281´)
If main pipe size is not increased,
ax2+bx2+cx2+dx2+ex2+fx2+gx2+h+i+j+k+l+m+n+p1000 m (3281´)
Each Y-joint ~
each indoor
h,I,j,..p45 m (148´)
Between indoor
units
The difference between the distance of the outdoor unit to the farthest indoor
unit and the distance of the outdoor unit to the farthest indoor unit 45m (148´)
(a+b+c+d+e+f+g+p)-(a+h) 45 m (148´)
Distribution kit Model Remarks
Allowable
From distribution kit to indoor unit 3m (10´) MEV-A13SA / MEV-A16SA (For 1 indoor unit)
For wall mounted&
ceiling indoor unit
From distribution kit to indoor unit 20m (66´ )
MXD-A13K116A / MXD-A13K200A / MXD-A16K200A /
MXD-A22K200A (For 2 indoor units)
MXD-A13K216A / MXD-A13K300A / MXD-A16K213A /
MXD-A16K300A (For 3 indoor units)
DVM PLUS3_IM_E_31180-1.indd 27 2009-10-16 ソタネト 2:10:30

Table of Contents

Other manuals for Samsung DVM PLUS III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung DVM PLUS III and is the answer not in the manual?

Samsung DVM PLUS III Specifications

General IconGeneral
BrandSamsung
ModelDVM PLUS III
CategoryAir Conditioner
LanguageEnglish

Related product manuals