installing the unit _35
ENGLISH
Indoor power supply must be separated from outdoor power supply.
Connect the communication cable among the outdoor units when combining the
outdoor units.
Connect the communication cable between indoor and outdoor units to the main
outdoor unit.
If the communication cable between indoor and outdoor units and the
communication cable among outdoor units are crossed, communication is not
available.
The length of the cable among the outdoor units should be under 30m(98´ 5˝ ) or less.
Do not multiplex the communication cable to prevent communication error.
Maximum wiring length between the outdoor unit and the farthest indoor unit is
1000m(3280´ 10˝).
Communication cable Communication cable