40
SETTING
Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Description Page Mode
Use Auto Change Over for
4-pipe only
(When setting SEG3) Standard
heating temp. offset
(When setting SEG3) Standard
cooling temp. offset
(When setting SEG3) Standard
for mode change Heating
→
Cooling
Display/
detail
Display Detail Display Detail Display Detail Display Detail Display Detail Display Detail
05
0
Follow product
option
0 0 °C (0 °F) 0 0 °C (0 °F) 0 1 °C (1.8 °F)
1
Use Auto
Change Over
for 4-pipe only
1 0.5 °C (0.9 °F) 1 0.5 °C (0.9 °F) 1 1.5 °C (2.7 °F)
2 1 °C (1.8 °F) 2 1 °C (1.8 °F) 2 2 °C (3.6 °F)
3 1.5 °C (2.7 °F) 3 1.5 °C (2.7 °F) 3 2.5 °C (4.5 °F)
4 2 °C (3.6 °F) 4 2 °C (3.6 °F) 4 3 °C (5.4 °F)
5 2.5 °C (4.5 °F) 5 2.5 °C (4.5 °F) 5 3.5 °C (6.3 °F)
6 3 °C (5.4 °F) 6 3 °C (5.4 °F) 6 4 °C (7.2 °F)
7 3.5 °C (6.3 °F) 7 3.5 °C (6.3 °F) 7 4.5 °C (8.1 °F)
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Description Page
(When setting SEG3) Standard
for mode change Cooling
→
Heating
(When setting SEG3) Required
time for mode change
---
Display/
detail
Display Detail Display Detail Display Detail Display Detail Display Detail Display Detail
1
0 1 °C (1.8 °F) 0 5 min.
---
1 1.5 °C (2.7 °F) 1 7 min.
2 2 °C (3.6 °F) 2 9 min.
3 2.5 °C (4.5 °F) 3 11 min.
4 3 °C (5.4 °F) 4 13 min.
5 3.5 °C (6.3 °F) 5 15 min.
6 4 °C (7.2 °F) 6 20 min.
7 4.5 °C (8.1 °F) 7 30 min.
Setting address of FCU KIT and installation option