7. EXPLANATION OF PARAMETERS
738
Mode Page
Abbre-
viation
Name and description
Standard
value
Unit
Setting
range
Remarks
1 3 PMUL Command pulse multiplier
Set the parameter so that the position
command pulse is multiplied by 1 to 63.
You can enable the setting by selecting the
PMUL input terminal with the Func3
parameter, then turning on the input.
1 1 to 63 Position control
4 ENCR Output pulse dividing ratio
This parameter is used for selecting the
dividing ratio of the encoder signal (A- and
B-phase).
Dividing ratio = β / α
Where,
α : 1 to 64, 8192
β : 1 (α = 1 to 64)
2 (α = 3 to 64)
1 to 8191 (α = 8192)
1/1 1 to
1/8192
5 LTG Low speed
This parameter is used for selecting a
revolution speed below which the low speed
alarm is output.
If you specify LTG (low speed) with the Func4
parameter, the LTG alarm is output as the
revolution speed goes below the setting.
When the P-PI automatic switching function is
enabled:
Proportional-plus-integral control when the
speed is lower than the LTG setting.
Proportional control when the speed is over
the LEG setting.
50 min
-1
0 to
32767