7. EXPLANATION OF PARAMETERS
7-47
Mode Page
Abbre-
viation
Name and description
Standard
value
Unit
Setting
range
Remarks
2 1 Func0 Amplifier function select 0
• This parameter selects whether external
signals are made effective or are forcibly
turned on internally. It also selects the
overtravel input logic, the encoder used
(between motor encoder and fully closed
encoder) and the multiplication factor of the
encoder.
0000-
0000
0, 1
( 3)
( 4)
1 This function is available only with a servo system that supports the fully closed
design.
2 Selecting a fully closed encoder does not change the divided output. Thus, when you
need a divided output for the fully closed encoder, set Func5 bit4 to "1".
3 When overtravel bits 3 and 4 are internally turned on, they become ineffective if the
overtravel input logic is b-contact. And, they are always in overtravel status if the
overtravel input logic is a-contact.
4 When changing the setting of bit 7 or 6, you must turn the control power off once prior
Switchin