46 ACU-280 SATEL
2nd digit – counting time: 0 (30 seconds), 1 (120 seconds), 2 (240 seconds) or 3 (unlimited
time).
AVD-100 (AVD-200)
Magnetic contact – do not configure.
Shock detector – enter 2 digits:
1st digit – sensitivity: from 1 to 8 (1 – minimum; 8 – maximum).
2nd digit – the number of shocks – the entered value is irrelevant.
ASP-100 (ASP-200)
Enter 2 digits:
1st digit – type of acoustic signaling: from 1 to 4 – see table 9.
2nd digit – maximum duration of signaling: 1 (1 minute), 2 (3 minutes), 3 (6 minutes) or 4
(9 minutes).
1
Two sound frequencies (1450 Hz/2000 Hz) alternating within
1 second.
2
Sound with rising frequency (from 1450 Hz to 2000 Hz) within
1 second.
3
Sound with smoothly rising and falling frequency (1450 Hz –
2000 Hz – 1450 Hz) within 1 second.
4
Sound with falling frequency (from 2000 Hz to 1450 Hz) within
1 second.
Table 9. Types of acoustic signaling available in the ASP-200 siren.
ASP-205 (ASP-215)
For each position taken on the list by the siren, enter 3 digits:
1st digit – maximum duration of signaling: 1 (1 minute), 2 (3 minutes), 3 (6 minutes) or 4
(9 minutes).
2nd digit – type of acoustic signaling: 0 (disabled), 1 (sound type 1), 2 (sound type 2) or 3
(sound type 3) – see table 10.
3rd digit – optical signaling: 0 (disabled) or 1 (enabled).
1
Two sound frequencies (1450 Hz/2000 Hz) alternating within
1 second.
2
Sound with rising frequency (from 1450 Hz to 2000 Hz) within
1 second.
3
Sound with falling frequency (from 2000 Hz to 1450 Hz) within
1 second.
Table 10. Types of acoustic signaling available in the ASP-215 siren.
ASW-100 (ASW-200)
Enter 0 (only remote control), 1 (remote or manual control) or 2 (remote or manual control,
but with option to manually block the remote control).
ASW-210
For each position occupied by the controller, enter 0 (relay can only be controlled via the
control panel), 1 (the input enables relay to be controlled with monostable switch) or 2
(the input enables relay to be controlled with bistable switch).