BkrWear . Ir [Protection Para / Condition Monitoring / BkrWear]
16.0A
Only available if:
• BkrWear . Mode = Counters, Wear Lev.•
5.6A . . . 10000.0A P.1
Rated current of the circuit breaker
BkrWear . N(Ir) [Protection Para / Condition Monitoring / BkrWear]
100
Only available if:
• BkrWear . Mode = Counters, Wear Lev.•
2 . . . 100000 P.1
Number of switching operations at the rated current of the circuit breaker
BkrWear . Isc [Protection Para / Condition Monitoring / BkrWear]
1120.0A
Only available if:
• BkrWear . Mode = Counters, Wear Lev.•
16.0A . . . 100000.0A P.1
Maximum short-circuit current of the circuit breaker
BkrWear . N(Isc) [Protection Para / Condition Monitoring / BkrWear]
10
Only available if:
• BkrWear . Mode = Counters, Wear Lev.•
1 . . . 50000 P.1
Number of switching operations at the maximum short-circuit current of the circuit breaker
9.22.2.3 BkrWear: Direct Controls
BkrWear . Reset [Operation / Reset]
False False, True
╚═▷ True or not true
P.1
Direct Command to reset the counters and the wear level of the circuit breaker.
9.22.2.4 BkrWear: Signals (Output States)
BkrWear . Active [Operation / Status Display / All Actives]
[Operation / Status Display / BkrWear]
Signal: active
116 WIC1 WIC1-2.0-EN-REF
9 Protection Parameter
9.22.2.3 BkrWear: Direct Controls