BkrWear . Alarm [Operation / Status Display / Alarms]
[Operation / Status Display / BkrWear]
Signal: Alarm: The maximum number of open commands or the maximum value for the sum of ruptured currents has
been exceeded.
BkrWear . Alm(mx.Sum.Tr) [Operation / Status Display / BkrWear]
Signal: Alarm: The maximum number of open commands has been exceeded.
BkrWear . Alm(mx.Sum.Itrip) [Operation / Status Display / BkrWear]
Signal: Alarm: The maximum value for the sum of ruptured currents has been exceeded.
BkrWear . Alm (CB Wear Lev.) [Operation / Status Display / BkrWear]
Signal: Alarm: The maximum wear level of the circuit breaker has been exceeded.
9.22.2.5 BkrWear: Values
BkrWear . Sum Itrip [Operation / Condition Monitoring / BkrWear]
Sum of the ruptured fault currents
BkrWear . Bkr Wear Level [Operation / Condition Monitoring / BkrWear]
Only available if:
• BkrWear . Mode = Counters, Wear Lev.•
Wear level of the circuit breaker. (100% means that the circuit breaker has to be maintained.)
9.22.2.6 BkrWear: Counters
BkrWear . Sum Trips [Operation / Condition Monitoring / BkrWear]
Sum of the previously executed open commands