indicator). Since the FIx are bistable the last state remains available even after the WIC1 and
DiggiMEC are no longer supplied (i. e. have been switched o󰊞).
All output relay contacts are potential-free. Each relay can be assigned a signal out of
the »assignment list«.
NOTICE!
Whenever the DiggiMEC is not actively used by a human operator we recommend to
keep the lid closed. (Depending on the local security directives you might also want to
use the sealing option.)
This prevents an unintended re-positioning of the 󰊠ag indicators / output relays.
Furthermore, it reduces the risk of dust or dirt intruding into the mechanics of the 󰊠ag
indicators.
Within menu branch [Device Para / DiggiMEC / FI / BO], set the following parameters for
each FIx:
»Assigned signal«: The parameter »FIx assign.« assigns a trigger signal to FIx.
With the setting »FIx latching« = “No latching”, the FIx continuously adopts the state
of the assigned signal.
If »FIx latching« is set to “With latching” or to “Latching w. Auto-Reset”, the state
that is set by the trigger signal is permanently stored. (For details see ╚═▷ “3.9.3.1
Latching”.)
Each FIx can only be reset – “acknowledged” – after the signal that had initiated its setting
has dropped out.
3.9.3.1 Latching
After the assigned signal has become active a latched FIx keeps its state until it is
acknowledged, or some automatic reset occurs.
A latched FIx gets reset only in any of the following cases and only after the assigned trigger
signal has dropped out.
The following latching modes are settable via [Device Para / DiggiMEC / FI /
BO] »FIx latching«:
“No latching” – The status of the 󰊠ag indicator immediately follows the status of the
assigned signal.
“With latching” – When the assigned signal gets active it sets the 󰊠ag indicator,
which stays set. After the assigned signal has dropped o󰊞 the 󰊠ag indicator can be
electrically reset by the device.
Latching w. Auto-Reset” – latching with automatic reset, see also ╚═▷ “Automatic
Reset”.
120 WIC1 WIC1-1.0-EN-MAN
3 Hardware
3.9.3.1 Latching

Table of Contents