Table of Output Functions
Set
value
Functions
Descriptions
0
Disabled
Output terminals without any function
1
Running
When the converter is running, output the close signal
It means that converter is running; closed signal is output.
2
Direction
On run reverse, output the close signal It indicates the
running direction of converter; closed signal is
output when it's running in reverse direction.
3
Fault output
When the converter is out of work, output the close signal
Closed signal is output when it's malfunctioning.
4
On standby
Establish main circuit and control circuit power, the
protection function of the converter is not change, and the
converter is running, output the close signal Major loop
and control circuit are established; protection function isn't
enabled; converter is on standby; closed signal is output.
5
Frequency
received
Please refer to the explanations of function code PA-11~13
6
FDT
ON: Running frequency reaches the value of P0-09
Signal "ON" is output when running frequency reaches
upper limiting frequency
7
Upper limiting
frequency
received
ON: Running frequency reaches the value of P0-10
Signal "ON" is output when running frequency is
equivalent to or lower than lower limiting frequency
8
Lower
frequency
limiting
received
ON: the value of count reach the setting value of PA-14
Signal "ON" is output when count value reaches the value
set by PA-14.
9
Setting count
value
received
Designated
count value
received
ON: the value of count reach the setting value of PA-15
Signal "ON" is output when count value reaches the value
set by PA-15.
10
11~15 Reserved Reserved
0 : Operating frequency
1 : Output current
2 : Bus voltage
3 :Output voltage
Default: 0
• The standard range of analogue input current/voltage is 0~20mA/0~10V,
which can be selected by Jumper 5. Output signals can be selected by the
setting of this parameter, which correspond to output frequency or output
current of converter.
Corresponding range of AO(0~10V/0~20mA) is as followed :
Descriptions
0~upper limiting frequency
0~double rated current
0~double rated voltage
0~double rated voltage
It's mainly not only applied to the correction of analogue output voltage
but also used to adjust the range of analogue output voltage. Analog output
voltage = Analogue output voltage × AO correction coefficient
• If the set value of parameter P6-03 is zero while the set value of
parameter P6-04 is 100%, the corresponding AO of upper limiting
frequency is +10V (20mA). AO correction coefficient can be increased
properly to calibrate the analogue output voltage if practical AO is only
9.8V because of differences of circuit.
Set value
Functions
0
1
Output current
2
Bus voltage
3
Output voltage
• When the inverter output signal when stop the machine open, until the
P6-05, the output signal to shut down.
P6-03
Ao1 options
Running frequency
Default:
100.0%
P6-04
0.0~250.0%
AO correction
coefficient
0
P6-05
0~3000.0S
Stop delay time
setting
53
52
PC-26
Stage 4
run time
0.0s(h)〜6553.5s(h)
0.0s(h)
PC-27
Section 4
acc. and dec.
time selection
0〜3 0
PC-28
5th run time
0.0s(h)〜6553.5s(h)
0.0s(h)
PC-29
0〜3 0
PC-30
Run time of
paragraph 6
0.0s(h)〜6553.5s(h)
0.0s(h)
PC-31
0〜3 0
PC-42
Run time in
paragraph 12
0.0s(h)〜6553.5s(h)
0.0s(h)
PC-43
The 12th
paragraph
acc. and dec.
time selection
0〜3 0
PC-50
Simple PLC
runtime unit
0:s(second)
1:h(hour)
0
PC-51
Multi-segment
instruction 0
given mode
0
Parameter
Name
Setting Range
Default
Prope-
rty
Modbus
Address
Fun-
ction
Code
Section 5
acc. and dec.
time selection
Section 6
acc. and dec.
time selection
PC-32
Run time of
paragraph 7
0.0s(h)〜6553.5s(h)
0.0s(h)
PC-33
0〜3 0
Section 7
acc. and dec.
time selection
PC-34
0.0s(h)〜6553.5s(h)
0.0s(h)
PC-35
0〜3 0
Section 8
acc. and dec.
time selection
8th run time
PC-36
PC-38
PC-40
0.0s(h)〜6553.5s(h)
0.0s(h)〜6553.5s(h)
0.0s(h)〜6553.5s(h)
0.0s(h)
0.0s(h)
0.0s(h)
PC-37
PC-39
PC-41
0〜3
0〜3
0〜3
0
0
0
Section 9
acc. and dec.
time selection
Section 10
acc. and dec.
time selection
Section 11
acc. and dec.
time selection
9th run time
Run time of
paragraph 10
Run time of
paragraph 11
Fun-
ction
Code
Parameter
Name
Setting range
Default
Prope-
rty
Modbus
Address
PC-44
Run time in
paragraph 13
0.0s(h)〜6553.5s(h)
0.0s(h)
PC-45
The 13th
paragraph
acc. and dec.
time selection
0〜3 0
PC-46
Run time in
paragraph 14
0.0s(h)〜6553.5s(h)
0.0s(h)
PC-47
The 14th
paragraph
acc. and dec.
time selection
0〜3 0
PC-48
Run time in
paragraph 15
0.0s(h)〜6553.5s(h)
0.0s(h)
PC-49
The 15th
paragraph
acc. and dec.
time selection
0〜3 0
0 : given by PC-00
1 : given by AI1
2 : AI2 given
3 : AI3 given (panel potentiometer)
4 : Pulse given
5 : PID given
6 : P0-08 can be modified by
UP/DOWN
User Manual
Chapter 5
User Manual
Chapter 5
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○